> Figure: Cover page for **Installation Manual**, with Linear PRO ACCESS logo; model labels **3000XLS** and **3200XLS**; **NCB**. Title: **DUAL Gate Operator System**. Black banner states: “In a DUAL gate system the LPA 3000XLS is the MASTER gate operator and the LPA 3200XLS is the SECOND gate operator.” Large heading: “PROFESSIONAL INSTALLATION RECOMMENDED!” Warning box includes triangular exclamation icons. UL/ETL Intertek Listed logo and GTO ACCESS SYSTEMS, LLC logo appear below. No dimensions, part numbers, torque, wire specifications, arrows, or step order shown.
# WARNING!
This equipment is similar to other gate or door equipment and meets or exceeds Underwriters Laboratory Standard 325 (UL 325). However, gate equipment has hazards associated with its use and therefore by installing this product the installer and user accept full responsibility for following and noting the installation and safety instructions. Failure to follow installation and safety instructions can result in hazards developing due to improper assembly. You agree to properly install this product and that if you fail to do so GTO Access Systems, (“GTO”) shall in no event be liable for direct, indirect, incidental, special or consequential damages or loss of profits whether based in contract tort or any other legal theory during the course of the warranty or at any time thereafter. The installer and/or user agree to assume responsibility for all liability and use of this product releasing GTO Access Systems, from any and all liability. If you are not in agreement with this disclaimer or do not feel capable of properly following all installation and safety instructions you may return this product for full replacement value.
**READ ALL INSTRUCTIONS CAREFULLY AND COMPLETELY** before attempting to install and use this automatic gate operator. This gate operator produces a high level of force. Stay clear of the unit while it is operating and exercise caution at all times.
All automatic gate operators are intended for use on *vehicular gates only*.
This product meets and exceeds the requirements of UL 325, the standard which regulates gate operator safety, by Underwriters Laboratories Inc.
For more information on the GTO ACCESS SYSTEMS full line of automatic gate operators and access controls visit our website at **www.linearproaccess.com**.
©2015 GTO Access Systems, LLC
Printed in China for GTO Access Systems, LLC.
R4818 06-03-16
## Page 2
# Class Rating
The LPA 3000XLS/3200XLS Gate Operators is intended for use with **vehicular swing gates in single family residential applications**. The operator is system certified to be in compliance with UL 325, current edition, as of publication date.
**Vehicular Gate Operator Class Categories:**
**Residential Vehicular Gate Operator—Class I:** A vehicular gate operator (or system) intended for use in a home of one-to-four single family dwelling, or a garage or parking area associated therewith.
**Commercial/General Access Vehicular Gate Operator—Class II:** A vehicular gate operator (or system) intended for use in a commercial location or building such as a multifamily housing unit (five or more single family units), hotel, garages, retail store, or other building servicing the general public.
**Industrial/Limited Access Vehicular Gate Operator—Class III:** A vehicular gate operator (or system) intended for use in an industrial location or building such as a factory or loading dock area or other locations not intended to service the general public.
**Restricted Access Vehicular Gate Operator—Class IV:** A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.
| Converting Metric Units to English Equivalents | | | |
|---|---:|---|---|
| **When You Know** | **Multiply By** | **To Find** | **Symbol** |
| centimeters | 0.3937 | inches | in. (or ") |
| meters | 3.2808 | feet | ft. (or ') |
| kilograms | 2.2046 | pounds | lb. (or #) |
| Converting English Units to Metric Equivalents | | | |
|---|---:|---|---|
| **When You Know** | **Multiply By** | **To Find** | **Symbol** |
| inches | 2.5400 | centimeters | cm |
| feet | 0.3048 | meters | m |
| pounds | 0.4535 | kilograms | kg |
| Converting Temperature | | | |
|---|---|---|---|
| deg. Celsius | (°C x 1.8) + 32 | deg. Fahrenheit | °F |
| deg. Fahrenheit | (°F-32) ÷ 1.8 | deg. Celsius | °C |
# FOR YOUR RECORDS
Please record the following information product serial number (located on right side of control box), be sure to keep all receipts for proof of purchase. Refer to this information when calling Linear PRO Access for service or assistance with your automatic gate opener.
Serial Number: ___________________________________ Date of Purchase: ________________
Place of Purchase: ___________________________________________________________________
## Page 3
# Table of Contents
| Section | Page |
|---|---:|
| Class Rating | inside cover |
| Please Read This First | ii |
| Important Safety Instructions | iii |
| Technical Specifications | 1 |
| Before You Begin | 2 |
| Determine Charging Option for Battery: Transformer OR Solar | 2 |
| Solar Panel and Gate Activity Chart | 2 |
| Check Direction of Gate Swing | 3 |
| Prepare the Gates | 3 |
| Gate Grounding | 3 |
| 3000XLS Parts List | 4 |
| 3200XLS Parts List | 5 |
| Tools Needed | 6 |
| Materials You may Need for the Installation: | 6 |
| Installation Overview | 7 |
| Install the Master Gate Operator | 7 |
| Install the Post Bracket Assembly | 8 |
| Check Clearance | 10 |
| Install Gate Bracket | 10 |
| Attach Operator | 10 |
| Install the Second Gate Operator | 11 |
| Install the Closed Position Stops | 11 |
| Mount Battery Box and Control Box | 13 |
| Connect Battery | 13 |
| Connect Operator Power Cables | 15 |
| Connect the Power Input | 17 |
| Control Board Settings | 19 |
| Set the Closed Position Limit (for Pull-To-Open Applications) | 19 |
| Adjust the Stall Force Setting | 21 |
| Set Auto Close Time | 21 |
| Program Your Personal Transmitter Setting | 22 |
| Control Board Settings | 23 |
| Connecting Accessories | 24 |
| Wiring Accessories | 24 |
| Connecting Other Auxiliary Devices (Sirens, Lights, etc.) | 25 |
| Push-To-Open Installation Information | 26 |
| Setting the Open Position Limit (Push-To-Open Installations) | 27 |
| Column Installation | 28 |
| Troubleshooting Guide | 29 |
| Voltage Readings | 30 |
| Repair Service | 31 |
| Accessories | 32 |
## Page 4
ii LPA 3000XLS/3200XLS Instruction Manual
# Please Read This First
> Figure: GTO ACCESS SYSTEMS, LLC logo.
Thank you for purchasing a Linear PRO Access 3000XLS/3200XLS. When correctly installed and properly used, your LPA 3000XLS/3200XLS operators will give you many years of reliable service. Please read the following information to ensure you have the correct system for your particular needs. This manual will enable you to properly install your 3000XLS/3200XLS Automatic Gate Operators.
The 3000XLS/3200XLS operators are designed for installation on pull-to-open dual leaf gates. The gates must not exceed 16 feet in length nor weigh more than 650 pounds* per leaf (please see Technical Specifications on page 1). The 3000XLS/3200XLS operators can be used on vinyl, aluminum, chain link, farm tube, and wrought iron gates. **Use on solid (wood) gates is not recommended. Solid surface gates have a high resistance to the wind. If the wind is strong enough, the operators will obstruct, stop, and blow fuses.**
The 3000XLS/3200XLS can be installed on push-to-open gates with the addition of two (2) push-to-open brackets ⊕ [R4388].
The 3000XLS/3200XLS operators accommodates extra transmitters, digital keypads, solar panels, push buttons, automatic gate locks, and other access control products. **These optional accessories are noted with the ⊕ symbol.**
The 3000XLS/3200XLS operators feature **adjustable stall force**. This safety feature makes the gates stop and reverse direction within two seconds when it comes in contact with an obstruction. The “MIN” setting means the gate will exert the minimum force on an obstruction before it stops and reverses direction.
The 3000XLS/3200XLS operators also have an **adjustable auto-close** feature. After the gates reach the fully open position, they can be set to remain open from 3 to 120 seconds before automatically closing. Pressing the transmitter button at any time after the gates fully open will cause them to close immediately. “OFF” is the factory setting; meaning the gates will stay open until you press the transmitter button (or keypad, etc.) again.
Please call Linear PRO Access at (800) 543-4283 for more information about our professional line of gate operators and accessories. Our Sales Department will be glad to give you the name and phone number of a Linear PRO Access dealer near you.
## BEFORE YOU BEGIN TO INSTALL YOUR AUTOMATIC GATE OPERATORS:
Read these instructions carefully and completely to become familiar with all parts and installation steps. You must read the installation manual for detailed instructions on gate operators safety and proper use of the gate operators.
> Figure: Wizard character icon beside the text “24/7 Troubleshooting Wizard: http://support.gtoinc.com”.
**24/7 Troubleshooting Wizard: http://support.gtoinc.com**
> Figure: Box containing a circular plus symbol and the text: “GTO Accessories are noted with this symbol in this Installation Manual. Information about accessories can be found on page 32 and at www.linearproaccess.com.”
GTO Accessories are noted with this symbol in this Installation Manual. Information about accessories can be found on page 32 and at **www.linearproaccess.com**.
## Page 5
**IMPORTANT SAFETY INSTRUCTIONS**
Because automatic gate operators produce high levels of force, consumers need to know the potential hazards associated with improperly designed, installed, and maintained automated gate operator systems. *Keep in mind that the gate operator is just one component of the total gate operating system.* Each component must work in unison to provide the consumer with convenience, security, and safety.
This manual contains various safety precautions and warnings for the consumer. Because there are many possible applications of the gate operator, the safety precautions and warnings contained in this manual cannot be completely exhaustive in nature. They do, however, provide an overview of the safe design, installation, and use of this product. **CAREFULLY READ AND FOLLOW ALL SAFETY PRECAUTIONS, WARNINGS, AND INSTALLATION INSTRUCTIONS TO ENSURE THE SAFE SYSTEM DESIGN, INSTALLATION, AND USE OF THIS PRODUCT.**
Precautions and warnings in this manual are identified with this warning symbol. The symbol identifies conditions that can result in damage to the operator or its components, serious injury, or death.
**Because GTO automatic gate operators are only part of the total gate operating system, it is the responsibility of the installer/consumer to ensure that the total system is safe for its intended use.**
---
# How To Manually Open and Close the Gate:
⚠ **CAUTION:** The gate can be opened and closed manually when the operator is disconnected. **ONLY** disconnect the operator when the power switch is **OFF** and the gate is **NOT** moving.
## Disconnecting the Operator
1. Turn operator power switch (Control Box) OFF.
2. Remove hairpin clip, clevis pin, and bushing from both the front and rear mounting points.
3. Remove the operator from the mount.
⚠ **CAUTION:** Because the *LPA* gate operator is battery powered, disconnect the operator **ONLY** when the power switch on the control box is turned **OFF**. Unplugging the transformer does not turn power to the operator **OFF**.
> Figure: Exploded drawing of the gate operator front mount. An operator push-pull tube connects to a **Gate Bracket** at the **Front Mount**. A **Clevis Pin** is inserted vertically through the connection, with a **Bushing** below it and a **Hairpin Clip** retaining it beneath. Arrows identify Front Mount, Clevis Pin, Gate Bracket, Bushing, and Hairpin Clip.
**NOTE:** Substitute a Pin Lock ⊕ [FM345] for the clevis pin on the front mount of the gate operator to prevent unauthorized removal of the operator from the gate.
> Figure: Drawing showing the operator front mount secured to the gate bracket using a pin lock and padlock. Part number: **[FM345]**.
LPA 3000XLS/3200XLS Instruction Manual iii
## Page 6
**IMPORTANT SAFETY INSTRUCTIONS**
# For The Consumer
⚠ **WARNING:** To reduce the risk of injury or death:
1. **READ AND FOLLOW ALL INSTRUCTIONS.** Failure to meet the requirements set forth in the instruction manual could cause severe injury or death, for which the manufacturer cannot be held responsible.
2. When designing a system that will be entered from a highway or main thoroughfare, make sure the system is placed far enough from the road to prevent traffic congestion.
3. The gate must be installed in a location that provides adequate clearance between it and adjacent structures when opening and closing to reduce the risk of entrapment. Swinging gates must not open into public access areas.
4. The gate and gate operator installation **must comply with any applicable local codes.**
## I. Before Installation
1. Verify this operator is proper for the type and size of gate, its frequency of use, and the proper class rating.
2. Make sure the gate has been properly installed and swings freely in both directions. Repair or replace all worn or damaged gate hardware prior to installation. A freely moving gate will require less force to operate and will enhance the performance of the operator and safety devices used with the system.
3. Review the operation of the system to become familiar with its safety features. Understand how to disconnect the operator for manual gate operation (page iii).
4. This gate operator is intended for vehicular gates ONLY. A separate entrance or gate must be installed for pedestrian use (page vi).
5. Always keep people and objects away from the gate and its area of travel. **NO ONE SHOULD CROSS THE PATH OF A MOVING GATE.**
6. Pay close attention to the diagram below and be aware of these areas at all times.
> Figure: Diagram of a double pull-to-open swing-gate driveway installation. Each gate is shown in its open position beside its gate post, with dashed swing paths extending toward the center of the driveway. Labels identify **ZONE 1** at the leading edges where the gates meet, **ZONE 2** between each gate and gate post, **ZONE 3** in each gate travel path, **ZONE 4** beside each fully open gate, and **ZONE 5** at pinch points between each operator and gate. Additional labels: **Gate in the Open Position** on both sides and **Driveway** in the center.
**Entrapment Zones for a proper Pull-To-Open installation:**
- **Zone 1** – leading edge of the gates.
- **Zone 2** – between the gate and the gate post.
- **Zone 3** – the path of the gate.
- **Zone 4** – the space between the gate in the open position and any object such as a wall, fence, etc.
- **Zone 5** – pinch points between the operator and gate.
iv LPA 3000XLS/3200XLS Instruction Manual
## Page 7
**IMPORTANT SAFETY INSTRUCTIONS**
## II. During Installation
1. Install the gate operator on the inside of the property and fence line. **DO NOT** install an operator on the outside of the gate where the public has access to it.
2. Be careful with moving parts and avoid close proximity to areas where fingers or hands could be pinched.
3. **Devices such as contact sensors (safety edges) and non contact sensors (photo beams) provide additional protection against entrapment.**
4. If push buttons or keypads are installed, they should be within sight of the gate, yet located at least 10 feet from any moving part of the gate (see diagram below). **Never install any control device where a user will be tempted to reach through the gate to activate the gate operator.**
5. Do not activate your gate operator unless you can see it and can determine that its area of travel is clear of people, pets, or other obstructions. Watch the gate through its entire movement.
6. Secure outdoor or easily accessed gate operator controls in order to prohibit unauthorized use of the gate.
> Figure: Double-gate driveway diagram showing shaded moving-gate areas. A dashed perimeter marks the gray prohibited area around the gates. Arrows show required clearances of **10'** above, below, and outward from each moving gate area. Labels: **Moving Gate Area** (twice), **Driveway**, and **NEVER INSTALL any control device within gray area**.
## III. After Installation
1. Attach the **warning signs (included)** to each side of the gate to alert the public of automatic gate operation. It is **your responsibility** to post warning signs on both sides of your gate. If any of these signs or warning decals become damaged, illegible or missing, replace them immediately. Contact LPA for free replacements.
2. The gate is automatic and could move at any time, posing a serious risk of entrapment. No one should be in contact with an activated gate when it is moving or stationary.
3. Do not attempt to drive into the gate area while the gate is moving; wait until the gate comes to a complete stop.
4. Do not attempt to “beat the gate” (drive through) while the gate is closing. This is extremely dangerous.
5. Do not allow children or pets near your gate. **Never let children operate or play with gate controls.** Keep ALL gate controls away from children and unauthorized users; store controls where children and unauthorized users do not have access to them.
6. **KEEP GATE AND GATE Operator PROPERLY MAINTAINED.** Always turn power to operator OFF before performing any maintenance. Regularly grease the gate hinges. Apply silicone spray to a soft, dry cloth and clean the push-pull tube at least once a month.
LPA 3000XLS/3200XLS Instruction Manual v
## Page 8
**IMPORTANT SAFETY INSTRUCTIONS**
7. To operate this equipment safely, YOU must know how to disconnect the operator for manual gate operation (page iii). If you have read the instructions and still do not understand how to disconnect the operator, contact the LPA Service Department.
8. Disconnect the operator **ONLY** when the power is **TURNED OFF** and the gate is **NOT** moving.
9. Make arrangements with local fire and law enforcement for emergency access.
10. Distribute and discuss copies of the **IMPORTANT SAFETY INSTRUCTIONS** section of this manual with all persons authorized to use your gate.
11. **IMPORTANT: Save these safety instructions. Make sure everyone who is using or will be around the gate and gate operator are aware of the dangers associated with automated gates. In the event you sell the property with the gate operator or sell the gate operator, provide a copy of these safety instructions to the new owner.**
Should you lose or misplace this manual, a copy can be obtained by downloading one from the Linear PRO Access web site (www.linearproaccess.com), by contacting GTO Access Systems., at 3121 Hartsfield Road, Tallahassee, Florida 32303 or by calling 1-800-543-4283 and requesting a duplicate copy. One will be provided to you free of charge.
# Required Safety Precautions for Gates
## Install Warning Signs
Warning signs alert people of automatic gate operation and are **required** when installing the GTO Gate Operator. The Warning Signs included must be installed on both sides of each gate. Furthermore, a walk-through gate must be installed for pedestrian traffic. We recommend using the **GTO Bulldog Pedestrian Gate Lock** ⊕ [FM145] for controlled access.
## Entrapment Protection
The gate operator’s inherent obstruction settings, even when properly adjusted, **may not be sensitive enough to prevent bodily injury in some circumstances.** For this reason, safety devices such as safety edge sensors (or photoelectric sensors), which stop and reverse gate direction upon sensing an obstruction, are suggested for enhanced protection against entrapment.
> Figure: Elevation drawing of a chain-link fence with a central double **Vehicular Gate** and a separate **Pedestrian Gate** at left. The pedestrian gate has a **Bulldog Pedestrian Gate Lock (recommended, not included)**. Both vehicular gates display a **Warning Sign**. Multiple **Contact Sensor (recommended, not included)** devices are shown at gate edges and along the bottom of the gates. **Photo Beam (recommended, not included)** devices are shown near both outer sides of the vehicular gate installation. Labels include Pedestrian Gate, Bulldog Pedestrian Gate Lock (recommended, not included), Warning Sign, Vehicular Gate, Contact Sensor (recommended, not included), and Photo Beam (recommended, not included).
vi LPA 3000XLS/3200XLS Instruction Manual
## Page 9
LPA 3000XLS/3200XLS Instruction Manual vii
# IMPORTANT SAFETY INSTRUCTIONS
## Secondary Means of Protection Against Entrapment
As specified by Gate Operator Safety Standard, UL 325 (30A.1.1), automatic gate operators shall have an inherent entrapment sensing system, and shall have provisions for, or be supplied with, at least one independent secondary means to protect against entrapment. The 3000XLS/3200XLS utilizes **Type A**, an inherent (i.e., built-in) entrapment sensing system as the **primary** type of entrapment protection. Also, the 3000XLS/3200XLS has **provisions for** the connection of **Type B1 or B2** protection to be used as the **secondary** type of entrapment protection, if desired.
1. For gate operators utilizing a non-contact sensor (e.g., photo-electric sensor– Type B1) in accordance with UL 325 (51.8.4 [h]):
A. Refer to the sensor manufacturer’s instructions on the placement of non-contact sensors for each type of application.
B. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate is still moving.
C. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as the perimeter reachable by a moving gate or barrier.
2. For gate operators utilizing a contact sensor (e.g., safety edge sensor– Type B2) in accordance with UL 325 (51.8.4 [i]):
A. One or more contact sensors shall be located at the leading edge, bottom edge, and post edge, both inside and outside of a vehicular swing gate system.
B. A hard wired contact sensor shall be located and its wiring arranged so that the communication between the sensor and the gate operator is not subjected to mechanical damage.
C. A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall be located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar obstruction. A wireless contact sensor shall function under the intended end-use conditions.
You may want to consider adding photo beams to your installation. GTO Photo Beams [R4222] provide a “non contact” means of entrapment protection.
> Figure: Diagram of a double vehicular swing gate installation. Labels identify “Leading Edge Contact Sensor on both sides of the gate” at the meeting edges; “Bottom Edge Contact Sensor on both sides of the gate” along the lower edges; “Post Edge Contact Sensor on both sides of the gate” at both outer post edges; “Photo Beam” at each side; and “Vehicular Gate” on each gate leaf. Gate operators are shown mounted horizontally on both leaves.
## ENTRAPMENT ALARM (UL 325; 30A.1.1A)
The 3000XLS/3200XLS Gate Operators are designed to stop and reverse within 2 seconds when a gate comes in contact with an obstruction. Additionally, these operators are equipped with an audio entrapment alarm which will activate if the unit obstructs twice while opening or closing. This alarm will sound for a period of 5 minutes, or until the operator receives an intended signal from a hard wired entry/exit source (e.g. push button control or keypad) and the gate returns to a fully open or fully closed position. Turning the power switch on the control box OFF and back ON will also deactivate the alarm. Wireless controls such as transmitters and wireless keypads will not deactivate the alarm.
## Page 10
viii LPA 3000XLS/3200XLS Instruction Manual
# IMPORTANT SAFETY INSTRUCTIONS
> Figure: Warning sign label. Orange header reads “WARNING” with warning-triangle symbol. Graphic shows a person beside a moving gate and a left-pointing arrow. Text reads: “Moving Gate Can Cause Injury Or Death”; “1. KEEP CLEAR! Gate may move at any time.”; “2. Do not allow children to operate gate or play in gate area.”; “3. This gate is for vehicles only. Pedestrians must use a separate entrance.”
*Warning signs (4 enclosed) to be installed on each side of the gate (3–5 feet above the bottom of the gate).*
> Figure: Product identification and manual operation instruction label for control box. Includes ETL/Intertek marking, “Conforms to UL STD 325,” “Certified to CSA STD C22.2 No.247,” and number “9901178.” Text reads: “3000XLS SERIES DC Swing Gate Operator”; “P/N LPA-3000XLS”; “Maximum Gate: 650 lb. (294.8 kg); 16 ft. (4.9 m)”; “Voltage: 12 Vdc; Frequency: 0 Hz; Power: 60 W”; “Class I & II Vehicular Swing Gate Operator.” “Serial Number: LPA3000XLS-0000000.” Manual-operation steps: “TO MANUALLY OPEN AND CLOSE THE GATE: 1. Turn control box power switch OFF. 2. Disconnect front or rear mount from mounting bracket. 3. Pull operator away from mounting brackets and move gate.” Warning: “Disconnect operator ONLY when the control box power switch is OFF and the gate is NOT moving.” Bottom text: “MMDDYY” and “GTO Access Systems, LLC - Tallahassee, Florida USA.”
*Product identification and manual operation instruction label (1) installed on control box.*
> Figure: Logo and warning label for master operator housing. Left portion reads “3000 PRO XLS,” “1-800-543-GATE,” “www.linearproaccess.com,” and “Linear PRO ACCESS™.” Right portion is a warning label reading “WARNING,” “MOVING GATE Can Cause Injury or Death,” with gate/person graphic and left-pointing arrow.
*Logo and warning labels (2) installed on each side of master operator housing.*
> Figure: Logo and warning label for second operator housing. Left portion reads “3200 PRO XLS,” “1-800-543-GATE,” “www.linearproaccess.com,” and “Linear PRO ACCESS™.” Right portion is a warning label reading “WARNING,” “MOVING GATE Can Cause Injury or Death,” with gate/person graphic and left-pointing arrow.
*Logo and warning labels (2) installed on each side of second operator housing.*
## Page 11
LPA 3000XLS/3200XLS Instruction Manual 1
# Technical Specifications
## GTO/ACCESS SYSTEMS 3000XLS/3200XLS AUTOMATIC GATE OPERATOR
### DRIVE
- Low friction screw drive (linear actuator) rated for -5 ºF to +160 ºF (-21 ºC to +71 ºC). Use of GTO battery heater FM316 (Not solar compatible) is recommended in extreme cold temperatures.
- Powered by a 12 V motor with integral case hardened steel gear reducer. Motor speed reduced to 375 rpm.
- Maximum opening arc of 110º. Approximate opening time (90º): 15-20 seconds, depending on weight of gate.
### POWER
- The system is powered by a 12 Vdc, 7.0 Ah, sealed, rechargeable acid battery.
- Battery charge is maintained by a 120 Vac, 18 Vac output transformer. Blade-style control board fuse is rated for 25 A.
NOTE: The transformer should not be directly connected to any battery. Do not replace fuses with higher ampere rated fuses; doing so will void your warranty and may damage your control board.
- For optional solar charging see page 2.
### CONTROL
- LPA microprocessor-based control board is set for pull-to-open gate installations. DIP switches can be adjusted to accommodate an optional kit for push-to-open gates (see Accessory Catalog).
- A circuit on the control board regulates charging. “Sleep draw” is 25 mA; “active draw” is 3 to 7 A.
- Auto-memorization of digital transmitter code.
- LPA remote-mounted RF receiver tuned to 318 MHz.
- Operator length with push-pull tube fully retracted is 40 1/4”, mounting point to mounting point, arm stroke 16” max.
- Minimum gate length is 5 ft.
- Adjustable auto-close (3 to 120 seconds), and stall force potentiometers.
- Power terminal block accommodates a transformer or solar panels (not both).
- DIP switches simplify setup of gate operator.
- Accessory terminal block fully compatible with LPA push button controls, digital keypads, loops detectors, etc.
- Control board allows connection of safety edge sensors and photoelectric sensors.
- Audio entrapment alarm sounds if unit encounters an obstruction twice while opening or closing.
### OPERATIONAL CAPACITY
- The Gate Capacity Chart shows approximate cycles, per day, you can expect from the LPA 3000XLS/3200XLS Automatic Gate Operators when powered with a transformer. Actual cycles may vary slightly depending upon the type and condition of gate and installation.
NOTE: BALL BEARING HINGES SHOULD BE USED ON ALL GATES WEIGHING OVER 250 LB.
> Figure: “GTO/ACCESS SYSTEMS 3000XLS/3200XLS Gate Capacity Chart.” Subtitle: “Estimated number of daily cycles, based on use with a transformer and one(1) 12 Volt battery.” Rows are gate length; columns are gate weight.
| Gate Length / Gate Weight | 50 lb. | 100 lb. | 150 lb. | 200 lb. | 300 lb. | 400 lb. | 500 lb. | 650 lb. |
|---|---:|---:|---:|---:|---:|---:|---:|---:|
| 16 ft. | 160 | 150 | 140 | 130 | 120 | 110 | 100 | 90 |
| 14 ft. | 170 | 160 | 150 | 140 | 130 | 120 | 110 | 100 |
| 12 ft. | 180 | 170 | 160 | 150 | 140 | 130 | 120 | 110 |
| 5 – 10 ft. | 190 | 180 | 170 | 160 | 150 | 140 | 130 | 120 |
To determine the number of cycles the gate operator will perform using solar panels, please see the specifications listed on page 2.
\* An operation cycle is one full opening and closing of the gate.
These specifications are subject to change without notice.
## Page 12
2 LPA 3000XLS/3200XLS Instruction Manual
# Before You Begin...
## 1. Determine Charging Option for Battery: Transformer OR Solar
> **NEVER USE TRANSFORMER AND SOLAR PANEL(S) AT THE SAME TIME.**
> **It will damage the control board.**
**IMPORTANT:**
- The 3000XLS/3200XLS’ 12 volt battery must be charged by either connecting the transformer (included) or solar panel kit [FM123] to the control board.
- The transformer is designed for indoor use. If the transformer can be plugged only into an outside electrical outlet, a weatherproof cover/housing (available at local electrical supply stores) must be used.
- If your gate is more than 1000 ft. from an AC power source, you will need to use at least 10 watts solar charging power to charge the battery [FM123]. Refer to the Solar Panel and Gate Activity chart below.
- All low voltage wire used with the GTO Gate Operator must be 16 gauge dual conductor, stranded, direct burial wire [RB509]. Do not run more than 1000 ft. of wire.
# Solar Panel and Gate Activity Chart
> Figure: Drawing of a solar panel on a support, shown beside explanatory text. The chart includes a map of the United States divided into labeled solar zones. Zone 1 covers the northern/central-east area; Zone 2 forms a band across the south-central and southeastern area; Zone 3 covers western, southern, and other indicated areas, including Alaska/Hawaii inset. No arrows or dimensions shown.
The table and map illustrate the maximum number of gate cycles to expect per day in a particular area when using from 10 to 30 watts of solar charging power. The figures shown are for winter (minimum sunlight).
| Winter Ratings for 12 V Single Gate | Zone 1 | Zone 2 | Zone 3 |
|---|---:|---:|---:|
| 10 watts | 4 | 8 | 13 |
| 15 watts | 7 | 13 | 20 |
| 20 watts | 10 | 18 | 27 |
| 25 watts | 13 | 23 | 34 |
| 30 watts | 16 | 28 | 41 |
Accessories connected to your system will draw additional power from the battery.
NOTE: A minimum of 10 watts solar charging power is needed to charge the batteries. Adding a second battery [RB500] will improve the number of gate cycles.
⊕ 10 Watt Solar Panel [FM123]
⊕ 5 Watt Solar Panel [FM122]
## Page 13
### 2. Check Direction of Gate Swing
The 3000XLS/3200XLS is designed for Pull-To-Open installations. Push-To-Open installations require a Push-To-Open Bracket [R4388]. Please refer to specific Push-To-Open Installation Information on page 26.
> Figure: Two gate-swing diagrams. Left: “Pull-To-Open (arm retracts to open)” with a curved arrow showing the gate swinging inward; label “Your Property.” Right: “Push-To-Open (arm extends to open)” with a curved arrow showing the gate swinging outward; label “Your Property.”
### 3. Prepare the Gates
- The gate must be plumb, level, and swing freely on its hinges.
- The gate must move throughout its arc without binding or dragging on the ground.
- Wheels must NOT be attached to the gate.
- Gates over 250 lb. should have ball bearing hinges with grease fittings.
- Post must be secured in the ground with concrete (minimizes twist/flex when the operator is activated).
- Make sure there is a stable area for mounting the gate bracket (this may require the addition of a horizontal or vertical cross member).
- We recommend you position the operator near the center-line of the gate to keep the gate from twisting and flexing, and to avoid back-splash from rain.
> Figure: Gate-installation drawing with labels: A – Level; B – Plumb; C – Free Swinging; D – Posts Secured in Concrete; E – Centerline Mounting; F – Good Working Hinges. A level is shown across the top of the gate, vertical levels are shown at each side, arrows identify the centerline mounting and hinges, and posts are shown set in concrete.
> Figure: Two gate drawings showing suggested reinforcement locations. Top drawing label: “Horizontal Cross Member.” Bottom drawing label: “Vertical Cross Member.”
### 4. Gate Grounding
- Shorter cable is better, 1 to 2 feet recommended.
- Bolt ring terminal at end of cable 4 - 6 inches above ground level.
**R4196 Kit Includes:**
1. Ground Rod Clamp
2. 6 AWG Wire (3 feet)
**NOTE:** No grounding system absolutely protects against lightning strikes. If installed correctly, a grounding system will help minimize damage to your gate opener.
> Figure: Metal gate post grounding diagram. A close-up shows a “Metal Gate Post,” a ring terminal attached to it, “6 AWG Wire” labeled 2 running to a “Ground Rod Clamp” labeled 1, and an “8 Foot Ground Rod.” Ground rod specification: “5/8” Copper Clad Steel (not included) - available at local homecenter and hardware stores -.” Arrows identify the post, wire, clamp, and rod.
## Page 14
### 5. 3000XLS Parts List
> Figure: Illustrated parts inventory, divided into “CONTROL BOX AND ELECTRICAL COMPONENTS,” “BRACKET BOX - HB301,” and “HARDWARE BAG - H301P.”
| Component | Quantity / Part Number |
|---|---:|
| Battery | (1) RB500 |
| Transformer | (1) RB570 |
| GTO Transmitter | (1) RB741 |
| Control Box | (1) |
| Receiver | (1) |
| Warning Signs | (2) |
| Customer Support Card | — |
| Master Gate Operator, LPA 3000XLS Arm | (1) |
| Power Cable | 6' |
| Bracket Box - HB301 | Quantity |
|---|---:|
| Post Bracket | (1) |
| Gate Bracket | (1) |
| Post Pivot Bracket | (1) |
| Closed Position Stop Plate | (1) |
| Hardware Bag - H301P | Quantity |
|---|---:|
| 8" Nylon Cable Tie | (14) |
| 3/8" x 8" Bolt | (4) |
| 3/8" x 3" Bolt | (2) |
| 1/2" x 2-3/4" Bolt | (2) |
| 3/8" x 2-1/2" Clevis Pin | (1) |
| 3/8" x 1-3/4" Clevis Pin | (1) |
| Hairpin Clip | (2) |
| 3/8" Washer | (12) |
| 3/8" Lock Washer | (6) |
| 3/8" Nut | (6) |
| 1/2" Washer | (2) |
| 1/2" Lock Nut | (2) |
| 3/8" x 1/2" Bushing | (1) |
| 3/8" x 3/16" Bushing | (2) |
| 2" Screw | (5) |
## Page 15
### 6. 3200XLS Parts List
> Figure: Illustrated parts inventory, divided into “BRACKET BOX - HB301” and “HARDWARE BAG - H301P.” The illustration shows the second gate operator arm with a 40' power cable and two warning signs.
| Component | Quantity / Part Number |
|---|---:|
| Second Gate Operator, LPA 3200XLS Arm | (1) |
| Power Cable | 40' |
| Warning Signs | (2) |
| Bracket Box - HB301 | Quantity |
|---|---:|
| Post Bracket | (1) |
| Gate Bracket | (1) |
| Post Pivot Bracket | (1) |
| Closed Position Stop Plates | (1) |
| Hardware Bag - H301P | Quantity |
|---|---:|
| 8" Nylon Cable Tie | (14) |
| 3/8" x 8" Bolt | (4) |
| 3/8" x 3" Bolt | (2) |
| 1/2" x 2-3/4" Bolt | (2) |
| 3/8" x 2-1/2" Clevis Pin | (1) |
| 3/8" x 1-3/4" Clevis Pin | (1) |
| Hairpin Clip | (2) |
| 3/8" Washer | (12) |
| 3/8" Lock Washer | (6) |
| 3/8" Nut | (6) |
| 1/2" Washer | (2) |
| 1/2" Lock Nut | (2) |
| 3/8" x 1/2" Bushing | (1) |
| 3/8" x 3/16" Bushing | (2) |
| 2" Screw | (5) |
## Page 16
### 7. Tools Needed
> Figure: Drawing of installation tools labeled: Drill; Drill Bit; Pliers; Level; Clamps — Small, Medium, Large; Adjustable Wrench; Open End Wrenches; Hack Saw; Pen; Phillips Head Screwdriver; Wire Stripper; Small Flat Head; Flat Head Screwdriver; Hammer; Center Punch; Tape Measure.
- Power Drill
- Pliers
- Level
- Tape Measure
- Wire Strippers
- Center Punch
- Open End Wrenches: 9/16” and 3/4”
- Drill Bits: 3/8” and 1/2”
- Hacksaw or Heavy Duty Bolt Cutters
- Small (Flat Head) Screwdriver
- Phillips Screwdriver
- C-Clamps: small, medium, and large
- Adjustable Wrench
- Extra person will be helpful
### 8. Materials You may Need for the Installation:
Depending on the type of gates and posts, you may need some additional materials/hardware.
- Low voltage wire [RB509]. Length depends upon the distance between the transformer power supply and the control box. (Page 17)
- If the gate is more than 1000’ away from an AC power source you will need to use at least one 10 watt Solar Panel [FM123] to trickle charge the battery. (Page 2)
- PVC Conduit. (Page 7)
- The diameter of the post should be at least 6” in order to mount the post bracket. (Page 7)
- Depending upon the diameter of the post, you may need longer bolts than those provided. Bolts should be at least 1” longer than the diameter of the post. (Page 7)
- Metal plate for wooden posts. (Page 7)
- A horizontal or vertical cross members or mounting plates may be needed to mount the operators to the gates. (Page 3)
- Some types of installations require U-Bolts. (Page 11)
- Surge protection for transformer. (Page 18)
- Weatherproof cover for transformer if installed outside. (Page 18)
- For push-to-open applications you must have two (2) PTO Brackets [R4388).
**IMPORTANT:**
The 3000XLS gate operator (6 ft. cable) will be installed on the gate on the same side of the driveway as the control box and they will be referred to as the MASTER gate and gate operator. The 3200XLS gate operator (40 ft. cable) will be installed on the gate on the opposite side of the driveway from the control box and they will be referred to as the SECOND gate and gate operator throughout this manual.
## Page 17
LPA 3000XLS/3200XLS Instruction Manual 7
# 9. Installation Overview
## Pull-To-Open Gates (Gate Opens into the Property)
The diagram shown below is an example of a Pull-To-Open installation on a chain link fence and dual gate. Mounting the operators on masonry columns requires special procedures; see Column Installation Information on page 28. Furthermore, if you have a Push–To–Open gate, see Push–to–Open Installation on page 26 before proceeding.
> Figure: Diagram of a dual chain-link gate installation. Labels: “Receiver”; “Gate Swings Evenly and Freely / Hung Firmly and Plumb”; “Control Box with Battery”; “120 Volt Indoor Transformer” with note “(surge protector not supplied)”; “Post Bracket Assembly”; “MASTER Gate Opener”; “SECOND Gate Opener”; “Gate Bracket”; “6' Power Cable”; “Closed Position Stop Plates”; “Run 1000' (max.) of low voltage wire to control box from transformer (wire not included).”; “PVC conduit (not included) to protect second opener power cable and low voltage wire from lawn mowers and weed eaters.”; and “Concrete Poured Around Gate Post.” Arrows identify the labeled components and wiring routes.
# Install the Master Gate Operator (3000XLS)
## Install the Post Bracket Assembly
The post bracket is designed to work on a flat post. Posts must be at least 6” square in order to bolt the post bracket. When using bolts to mount the post bracket, the bolts must completely penetrate the post.
- The best method of attaching the post bracket to a metal post is welding.
- If your post exceeds 8”, it will be necessary to use hex head bolts longer than those supplied.
- Round wood posts (no smaller than 8” diameter) may be notched to create a flat surface for attaching the post bracket.
- Wood posts will require a metal plate (not provided) between the nuts and post to prevent the operator from pulling the bolts and washers through the wood.
- A post smaller than 6” in diameter should be made of metal instead of wood so that it will remain stable while the operator is moving the gate.
- Masonry columns will require masonry anchors/hardware (not provided).
> Figure: Exploded drawing of post bracket assemblies mounted to a square post and a round post. Shows bracket plates, bolts, washers, nuts, and a metal reinforcement plate behind a wood post. No readable labels in the drawing.
## Page 18
LPA 3000XLS/3200XLS Instruction Manual 8
### Step 1
Close the gate and place your level against the horizontal cross member. Position the level so that the top should be in the center of the cross member and overlaps the post. Scribe a line across the cross member and post. You will use this line to help determine position of post and gate brackets.
> Figure: Gate elevation showing a level placed along the horizontal cross member and extending over the gate post. A dashed horizontal scribe line crosses the gate and post. Inset side view shows the level and dashed line across gate members and post.
### Step 2
Position the post bracket on the post with the mounting holes centered over the scribe line. The post bracket should be flush with the edge of the post closest to the gate. Mark the position of post bracket holes on the post.
> Figure: Gate elevation showing a post bracket positioned on the gate post with mounting holes centered on the dashed scribe line.
### Step 3
Drill holes through post as marked using a 3/8” drill bit. Install the post bracket using the 3/8” x 8” hex head bolts and 3/8” flat washers, lock washers, and nuts (provided).
> Figure: Exploded drawing of a post bracket installed through a square wood post with long bolts and a reinforcement plate. Label: “Metal reinforcement plate for wood post.”
### Step 4
Place the end of post pivot bracket with two holes inside the post bracket. (Notched end of Post Pivot Bracket should face gate, to accommodate the operator arm.) Align the back hole in the post pivot bracket with back hole in the post bracket.
Insert 3/8” x 3” hex head bolt and washer through post pivot bracket and post bracket and secure with 3/8” washer, lock washer and nut.
> Figure: Exploded drawing of post pivot bracket within post bracket. Labels and arrows: “3/8" x 3" Bolt”; “3/8" Washer” (above bracket); “Post Bracket”; “3/8" Washer” (below bracket); “3/8" Lock Washer”; “3/8" Nut”; “Post Pivot Bracket.” The notched end of the pivot bracket faces toward the gate.
## Page 19
LPA 3000XLS/3200XLS Instruction Manual 9
### Step 5
Position the operator rear mount between post pivot bracket. Place a 1/2” bushing above the rear mount and a 3/16” bushing under the rear mount. Align the hole in rear mount, bushings and post pivot bracket and secure with the 2 1/2” clevis pin and hair pin clip.
> Figure: Exploded drawing of operator rear mount attached to post pivot bracket. Labels: “3/8” x 2-1/2” Clevis Pin”; “3/8” x 1/2” Delrin Bushing”; “Operator”; “Hairpin Clip”; and “3/8” x 3/16” Delrin Bushing under rear mount.”
### Step 6
Place a 3/16” bushing under the front mount and attach the gate bracket to the front mount using the 1 3/4” clevis pin and hairpin clip.
> Figure: Exploded drawing of the front mount and gate bracket. Labels: “Front Mount”; “3/8” x 1-3/4” Clevis Pin”; “Gate Bracket”; “3/8” x 3/16” Delrin Bushing under front mount”; and “Hairpin Clip.”
# Check Clearance
### Step 7
Open the gate to the desired open position. Position the operator so that the gate bracket rests against the gate along the level scribed line. Check the clearance between the operator and the gate. The operator should only make contact with the gate at the gate bracket. There should be a minimum clearance of 2” between the widest part of the operator arm and the gate.
When you have achieved the best position for the post pivot bracket in the open position, insert the 3/8” x 3” bolt and 3/8” flat washer through the aligned holes of the post bracket and post pivot bracket to hold it in place.
Clamp the gate bracket to the gate using c-clamps or another type of clamp.
**IMPORTANT:** While determining the position of the post pivot bracket, be sure that the position allows for minimum 2“ of clearance between the gate and the operator in both the open and closed positions. This clearance will give the operator the most efficient leverage point for opening and closing the gate and, more importantly, provides the least possible pinch area.
> Figure: Vertical diagram of gate in open position with the operator arm fully retracted. Labels: “Gate in the OPEN POSITION (Arm fully retracted)”; “Pinch Area”; “2" minimum”; and “Clamp.” Arrow indicates the pinch area between operator and gate; dimension arrow specifies 2-inch minimum clearance.
## Page 20
LPA 3000XLS/3200XLS Instruction Manual 10
### Step 8
Remove the clevis pin from the front mount and while supporting the gate operator, swing the gate and gate operator to the closed position. With the gate and gate operator in the closed position check the clearance and be sure that the gate operator is not binding at the post pivot bracket.
If you don’t have 2” clearance or the gate operator is binding on the post pivot bracket, remove the bolt in the post bracket and readjust the pivot bracket until you can achieve the proper clearance.
With the post pivot bracket in the optimum position for clearance and freedom of movement, replace the bolt in a post bracket adjustment hole and secure with 3/8” washer, and lock nut. Return the operator to the open position and reattach the gate bracket. Recheck the gate operator level and clearance in the open position. Adjustment of the gate bracket will be necessary if the post bracket was moved. After verifying clearance, make sure the gate bracket is clamped securely.
> Figure: Side-view diagram of gate in closed position with operator arm. Labels: “Gate in the CLOSED POSITION”; “Pinch Area”; “2" minimum”; “MAX 16"”; and “Clamp.” A clamp holds the gate bracket at the gate. An inset shows the post pivot bracket bolt, washer, and nut arrangement.
# Install Gate Bracket
### Step 9
Detach the front mount from the gate bracket. Check that the gate bracket holes are centered over the scribe line. Mark the gate in the center of the gate bracket holes. Remove the gate bracket and drill the 1/2” holes through the gate cross member and attach the gate bracket using the 1/2” x 2 3/4” bolts, washers and lock nuts.
> Figure: Diagram showing operator front mount and gate bracket below a “LEVEL horizontal cross member.” Label: “Mark cross member through middle of gate bracket slots and drill 1/2" holes.” Below are mounting examples labeled “FRONT VIEW” and “SIDE VIEW” for “Round Tube & Chain Link Gate” and “Square Tube Gate.” Decorative-gate example is labeled “Mounting Plate Created for Decorative Gate (required but not supplied).”
# Attach Operator
### Step 10
Make sure the gate is in the open position and the operator arm is fully retracted. Attach the operator to the securely bolted post bracket assembly and gate bracket using clevis pins, bushings, and hairpin clips, or optional Pin Lock [FM345]. Verify that the operator is level, bolts are tight, and adjust the post bracket assembly if necessary.
> Figure: Perspective drawing of operator attached between fence post and open gate. Labels: “Gate In Open Position”; “Level Operator”; “Clevis Pin, Bushing, and Hairpin Clip”; and “Fence Post.”
## Page 21
# Install the Second Gate Operator (3200XLS)
The hardware installation for the 3200XLS is the same as the 3000XLS - follow Steps 1 to 10 on pages 8 - 10 to install the 3200XLS on the second gate.
# Install the Closed Position Stops
The 3000XLS/3200XLS Gate Operators firmly hold the gates in the closed position using positive stops. The positive stops help stabilize the gate leaves in the closed position. To further enhance stability and security, we strongly recommended using an optional GTO Automatic Gate Lock.
**IMPORTANT:** The gate and gate operator on the same side as the control box will be referred to as the MASTER gate and gate operator. The gate and gate operator on the opposite side of the driveway from the control box will be referred to as the SECOND gate and gate operator.
**Note:** Ground stop required for GTO automatic gate lock.
> Figure: Illustration A. Top-view diagram of two closed gate leaves. The left leaf is labeled **MASTER GATE** and the right leaf **SECOND GATE**. Labels identify the **Control Box** at the master-gate side, **Gate Hinge** at each outer hinge, **Closed Position Stop Plates** at the meeting point, and **Optional Ground Stop (beneath gate)**. Curved arrows show each gate leaf can open “up to 110° (max.).”
### Step 1
Detach the gate operators from the gates and move the gates to their closed position (Illustration A). Using appropriate hardware for your type of gate (U-bolts for tube or chain link; screws or bolts for wood or metal) attach the closed position stop plate (horizontally) in line with the operator arm, about mid height on the MASTER gate frame. Do not tighten it completely at this time. Slide the stop plate toward the frame of the SECOND gate leaf until they touch (Illustration B). Once you have moved the stop plate to the correct position, tighten its hardware completely.
> Figure: Illustration B. Diagram titled “Closed Position Stop Plate mounted horizontally on metal post with U-bolts.” Front view shows a horizontal stop plate bolted between two gate-frame members. Top view shows circular tube frames labeled **MASTER Gate Frame** and **SECOND Gate Frame**, with the stop plate and U-bolts joining them. Labels: “FRONT VIEW” and “TOP VIEW.”
## Page 22
**NOTE:** The optional ground stop post is used to provide a secure point for the SECOND gate to close against. If you will be using the GTO Automatic Gate Lock accessory with your gate operator system, the low profile ground stop is **REQUIRED**, as example shown in illustration C.
### Step 2
Install a low profile ground stop (not provided) beneath the SECOND gate stop plate.
The ground stop needs to be positioned near the end of the gate as shown in Illustration A and may be made of metal or concrete and should be firmly secured in the ground (we recommend setting it in concrete).
### Step 3
Attach a vertical closed position stop plate to the SECOND gate.
Using appropriate hardware for your type of gate attach the vertical closed position stop plate to the SECOND gate frame at the point where it will come in contact with the ground stop post. Do not tighten it completely at this time. You must slide the closed position stop plate toward the ground stop until they touch (Illustration C). Once you have moved the stop plate to the correct position, tighten its hardware completely.
> Figure: Illustration C. Diagram captioned “Closed Position Stop Plate mounted on the gate leaf that CLOSES FIRST.” Front view shows a stop plate mounted vertically, with a vertical double-headed arrow labeled “Mount Vertically.” Side view shows the vertical **Closed Position Stop Plate** contacting a **Low Profile Ground Stop in Near the Center of Driveway**. Labels: “FRONT VIEW,” “SIDE VIEW,” and “Illustration C.”
### Step 4
Return gates to the open position and reattach gate operators.
> Figure: Diagram of both gates in the open position, each attached to a gate operator at its post. Curved dashed arcs show the leaves swung open toward the center of the **Driveway**. Both leaves are labeled “Gate in the Open Position.”
## Page 23
# Mount the Battery Box and Control Box
### Step 1
Remove the Control box from the Battery Box by removing four screws as shown in *Illustration A*.
> Figure: Illustration A. Open battery box/control box assembly. Four screws above the box have upward arrows indicating removal. The control-box cover is open at left.
### Step 2
Mount the Battery Box using the screws (provided) or another secure mounting method as shown in *Illustration B*.
The battery/control box must be mounted at least 3 feet above the ground to protect it from rain splash, snow, etc., and at least 3 feet from an AC power source to prevent electrical interference.
> Figure: Illustration B. Battery box mounted to a vertical surface. Dashed lines identify mounting screws at the upper and lower mounting locations. An “UP” arrow is visible inside the box.
### Step 3
Slide the battery into position with the terminals to the right as shown in *Illustration C*.
> Figure: Illustration C. Battery is shown sliding into the battery box from the right, indicated by a left-pointing arrow. The battery terminals are on the right side.
# Connecting the Battery
### Step 4
Verify that the ON/OFF switch on the Control Box is in the OFF position. *Illustration D*.
Connect the BATTERY WIRE HARNESS wires to the battery --- RED wires to POSITIVE (+) battery terminal and BLACK wires to NEGATIVE (–) battery terminal.
The BATTERY WIRES from the CONTROL BOARD should extend through the KNOCK-OUT in the back of the CONTROL BOX. Plug the BATTERY HARNESS wires into the wires coming from the CONTROL BOX.
> Figure: Illustration D. Closed control box with a magnified view of the switch labeled “ON/OFF.” The switch is shown in the OFF position.
> Figure: Battery wiring diagram. A battery box and control-box back are connected by red and black battery harness wires and plug connectors. Arrows label **Red to Positive (+)** and **Black to Negative (–)** at the battery terminals. A label points to **Connectors for second battery.**
## Page 24
### Step 5
Tuck the excess battery leads into the battery box and reattach the CONTROL BOX to the BATTERY BOX.
> Figure: Open control box showing the control board. Four arrows point toward the mounting locations, showing screws being installed to reattach the control box.
# Mounting the Receiver
### Step 1
Temporarily mount the receiver at this time. You will need to use the transmitter (page 22) to check the range of the receiver *before permanently mounting* it. You may have to try different locations before permanently mounting the receiver. The receiver range can vary from 50 to 100 feet depending upon weather, topography, and external interference.
**Mount the receiver:**
- Ensuring a line-of-sight between transmitter and antenna.
- At least 3 feet away from AC voltage.
- As high as possible for optimum range.
- DO NOT mount receiver upside down.
- DO NOT mount receiver on metal fence or post (this will decrease signal range). If attaching receiver to metal fence, you should mount receiver on a piece of wood attached to the fence (see illustration).
**The receiver cable:**
- Cable length is 10 ft. (receivers with longer cables are available as special order items; call the GTO Sales Department).
- NEVER splice receiver cable!
- Run the receiver cable through PVC conduit to protect it from damage.
- DO NOT run cable in conduit containing AC wiring.
> Figure: Receiver mounted on a piece of wood attached to a fence post. The receiver has a vertical antenna and a cable hanging downward. An arrow labels “Receiver mounted on piece of wood.”
This device complies with FCC rules Part 15. Operation is subject to the following conditions:
1. This device may not cause harmful interference.
2. This device must accept an interference that may cause undesired operation.
Transmitter distance may vary due to circumstances beyond our control. NOTE: The manufacturer is not responsible for any radio or TV interference caused by unauthorized modifications to this equipment. Such modifications could void the user’s authority to operate the equipment.
## Page 25
# Connect Operator Power Cables
### Step 1
Review the Installation Overview illustration below before proceeding.
Cut a slot into the driveway to accommodate 3/4” PVC conduit (not provided). The buried conduit will protect the SECOND operator power cable from automobile tires, lawn mower blades, weed eaters, and grazing animals. Pull the SECOND operator power cable through the conduit, up to the Control Box.
> Figure: Installation overview drawing of two gates in the open position with operators installed. Labels and arrows identify: “Receiver”; “Control Box”; “MASTER Gate Operator”; “SECOND Gate Operator”; “Power Cable from MASTER Gate Operator”; “Power Cable from SECOND Gate Operator”; and “PVC conduit *(not included)* to protect SECOND operator power cable from lawn mowers and weed eaters.” The conduit runs beneath the driveway between the gates. Center text reads: “GATES IN THE OPEN POSITION WITH OPERATORS INSTALLED.”
### Step 2
Loosen sealing nuts on strain relief hubs at bottom of control box. Insert power cables into control box through strain reliefs. Thread approximately 6” to 8” of the power cables into the control box and retighten sealing nuts until the power cables lock into place.
> Figure: Exploded drawing of a strain relief assembly. Labels identify, from top to bottom: “Lock Nut,” “Hub,” and “Sealing Nut.” Vertical label: “Strain Relief.”
> Figure: Drawing of an open control box with power cables entering through the bottom. Arrows identify “Strain Relief,” “Power Cable from Master Operator,” and “Power Cable from Second Operator.”
## Page 26
# Connecting MASTER Operator
### Step 3
Insert the stripped power cable wires into the appropriate terminals on the MASTER OPERATOR terminal block. The green wire should be inserted into the GRN terminal, the white wire into WHT, the blue wire into BLU, brown wire into BRN, orange wire into ORG, red wire into RED, and the black wire into the BLK terminal.
Tighten the set screws against the end of the wires.
> Figure: Control-board terminal diagram showing “Power Cable from the Master Operator Arm” connected to the “MASTER OPERATOR” terminal block. Terminal labels, top to bottom: GRN, WHT, BLU, BRN, ORG, RED, BLK. Additional visible board labels: “CONTROL INPUTS,” COM, COM, CYCLE, SAFETY, EXIT, SHADOW, CLOSE EDGE, OPEN EDGE, “GTO RCVR.”, GRN, BLK, RED, and “RECEIVER.”
> Figure: Three wire-terminal connection drawings labeled “Correct,” “Wrong,” and “Wrong.” The correct example is labeled “Wire.” The wrong examples are labeled “Screwed into wire insulation” and “Exposed strands of wire.”
> Figure: Warning box: “NEVER SPLICE WIRES Splicing permits corrosion and seriously degrades the wire's ability to carry an adequate current.”
# Connecting SECOND Operator
### Step 4
Insert the stripped wires of the power cable into the appropriate terminals on the SECOND OPERATOR terminal block. The green wire should be inserted into the GRN terminal, the white wire into WHT, the blue wire into BLU, brown wire into BRN, orange wire into ORG, red wire into RED, and the black wire into the BLK terminal.
Tighten the set screws against the end of the wires.
> Figure: Control-board terminal diagram showing “Power Cable from the Second Operator Arm” connected to the “2ND OPERATOR” terminal block, and the master cable connected below. SECOND OPERATOR terminal labels, top to bottom: GRN, WHT, BLU, BRN, ORG, RED, BLK. Visible labels include “CONTROL OUTPUTS,” PWR, LOCK, RLY, AUX, “2ND OPERATOR,” “MASTER OPERATOR,” COM, COM, and CYCLE.
## Page 27
# Connect the Power Input
**IMPORTANT:**
- The transformer is designed and intended for indoor use. If the transformer can only be plugged into an outside electrical outlet, a weatherproof cover/housing (available at local electrical supply stores) must be used.
- The only wire acceptable for use with GTO products is 16 gauge stranded, low voltage, direct burial wire [RB509]. This particular gauge enables the transformer to provide an adequate charge through the control board to the battery at distances up to 1000 ft.
- DO NOT use telephone wire or solid wire.
- NEVER splice wires. Splicing permits corrosion and seriously degrades the wire’s ability to carry an adequate current.
- **NEVER USE TRANSFORMER AND SOLAR PANEL(S) AT THE SAME TIME! Doing so will damage the control board.**
- If your gate is more than 1000 ft. from an AC power source, you will need to use at least 10 watts solar charging power [FM122/FM123] to charge the battery. Refer to the Solar Panels and Gate Activity Chart on page 2.
### Step 1
Make sure the control box power switch is OFF.
> Figure: Drawing of the control box with a magnified view of its switch. The switch is labeled “ON/OFF,” with an arrow pointing to it.
### Step 2
Select the electrical outlet outlet into which you will plug the transformer. Measure the distance from this outlet to the control box following the path where the wire will be laid (allow for an additional 6” to be pulled into the control box).
### Step 3
Lay the low voltage wire in a trench following a path from the selected electrical outlet to the control box. Wires coming up from the ground should be run through PVC conduit to protect them from lawn mower blades, weed eaters, and grazing animals. Bury the wire in the trench.
### Step 4
Feed the low voltage wires upward through the strain relief opening on the lower left of the control box. Pull 6” to 8” of wire into the control box.
> Figure: Drawing of an open control box showing low-voltage wire entering from a vertical “PVC Pipe” at the lower left. Arrows label “Low Voltage Wire from Transformer” and “Operator Power Cables.”
## Page 28
### Step 5
Strip 3/16” off the ends of the low voltage wire and twist tightly. Attach these ends to the **18 VAC or SOLAR** terminals located on the POWER INPUTS terminal block. **Be certain not to let the exposed wires touch each other!**
Insert one transformer wire into an **18 VAC or SOLAR** terminal. Insert the other transformer wire into the remaining **18 VAC or SOLAR** terminal. The transformer wires can be connected to the **18 VAC or SOLAR** terminals regardless of color/polarity.
Tighten set screws against exposed end of wires.
> Figure: Control-board terminal diagram showing red and black “Low Voltage Wire from AC Transformer or Solar Panel” connected to the POWER INPUT terminals. Labels include “TRANSF. OR GTO 18 VOLT SOLAR PANEL,” “POWER INPUT,” “CONTROL OUTPUTS,” PWR, LOCK, RLY, AUX, “2ND OPERATOR,” and “MASTER OPERATOR.” The red and black wires are labeled “RED” and “BLACK.”
### Step 6
At the transformer, strip 1/2” of insulation from the ends of the low voltage wire. Twist tightly and attach wires to the transformer terminals.
**Make sure the exposed wires do not touch each other!**
> Figure: Drawing of a plug-in transformer with low-voltage wires attached at its terminals. A screwdriver is shown tightening a terminal screw.
### Step 3
Plug the transformer into the electrical outlet. (Use of a surge protector with the transformer is strongly recommended.)
IMPORTANT: This is a class II indoor transformer; if using transformer outdoors be sure to enclose it in a weatherproof case.
> Figure: Drawing of a “Class 2 Transformer” plugged into a “SURGE PROTECTOR,” which is plugged into a wall electrical outlet.
## Page 29
**Control Board Settings**
### Set Closed Position Limit (for Pull-To-Open Applications)
**Step 1**
Power switch is on, gates are in the **OPEN** position, operator arms fully retracted.
> Figure: Diagram of two gate operators with gates in OPEN position. Left side is labeled “Control Box” with an arrow to the control box, and “Master Gate Operator.” Right side is labeled “Second Gate Operator.” Center label: “Gates in OPEN Postion.” Inset drawing shows the operator power switch labeled “ON/OFF.”
**Step 2**
Press the transmitter to activate operator arms. The gates will begin to **CLOSE**.
> Figure: Diagram of master and second gate operators beginning to close. Curved arrows indicate gate movement inward. Center label: “Gates Closing.” Left labels: “Control Box” and “Master Gate Operator.” Right label: “Second Gate Operator.” Inset shows a transmitter.
**Step 3**
When either gate reaches **CLOSED** position, press transmitter to stop the gates.
**A.** If the master gate reaches closed position first - press and hold LEARN MAST LIMIT for 5 seconds, or until buzzer beeps to set closed position.
**B.** If the second gate reaches closed position first - press and hold LEARN 2ND LIMIT for 5 seconds, or until buzzer beeps to set closed position.
> Figure: Two gate-position diagrams. Upper diagram is labeled “A. Master Gate Closed”; lower diagram is labeled “B. Second Gate Closed.” Both show the gates closed across the opening. Left-side labels include “Control Box.”
>
> Figure: Transmitter illustration.
>
> Figure: Control-board button detail labeled “LEARN MAST LIMIT,” “A,” and “Learn Master Limit Button,” with an arrow pointing to the button.
>
> Figure: Control-board button detail labeled “LEARN 2ND LIMIT,” “B,” and “Learn 2ND Limit Button,” with an arrow pointing to the button.
LPA 3000XLS/3200XLS Instruction Manual 19
## Page 30
**Step 4**
Press the transmitter to open the gates. Gates will **OPEN** fully. The gate in step 3A or 3B is now programmed.
> Figure: Diagram of two gate operators with gates in OPEN position. Center label: “Gates in OPEN Postion.” Left labels: “Control Box” and “Master Gate Operator.” Right label: “Second Gate Operator.” Inset shows a transmitter.
**Step 5**
Press the transmitter to activate operator arms. The gates will begin to **CLOSE**.
> Figure: Diagram of master and second gate operators closing. Curved arrows indicate inward movement. Center label: “Gates Closing.” Left labels: “Control Box” and “Master Gate Operator.” Right label: “Second Gate Operator.” Inset shows a transmitter.
**Step 6**
The gate that was programmed in step 4 will stop on its own. Press the transmitter again to stop the other gate when it reaches the desired **CLOSED** limit.
**A1.** Master gate reaches closed position. - press and hold LEARN MAST LIMIT for 5 seconds, or until buzzer beeps to set closed position.
(Master gate is now programmed)
**B1.** 2nd gate reaches closed position - press and hold LEARN 2ND LIMIT for 5 seconds, or until buzzer beeps to set closed position.
(Second gate is now programmed)
> Figure: Diagram of both gates in the closed position. Center label: “Gates in Closed Position.” Left labels: “Control Box” and “Master Gate Operator.” Right label: “Second Gate Operator.”
>
> Figure: Transmitter illustration.
>
> Figure: Control-board button detail labeled “LEARN MAST LIMIT,” “A1,” and “Learn Master Limit Button,” with an arrow pointing to the button.
>
> Figure: Control-board button detail labeled “LEARN 2ND LIMIT,” “B1,” and “Learn 2ND Limit Button,” with an arrow pointing to the button.
**Step 7**
Press the transmitter once again to **OPEN** gates.
Both gates closed position are now programmed.
If you make a mistake and set the limit at the wrong position: press your transmitter to return the gate to the fully opened position, then press and hold the LEARN MAST LIMIT and/or the LEARN 2ND LIMIT button for 5 seconds. This will clear the memory for the closed limit position. Repeat Steps 1-6.
> Figure: Diagram of gates returned to OPEN position. Center label: “Gates in OPEN Postion.” Left labels: “Control Box” and “Master Gate Operator.” Right label: “Second Gate Operator.” Inset shows a transmitter.
20 LPA 3000XLS/3200XLS Instruction Manual
## Page 31
### Adjust the Stall Force Setting
The Stall Force potentiometer on the control board controls the obstruction sensitivity (or the amount of force the operator will apply to an obstruction for two (2) seconds before it automatically stops and reverses direction).
**IMPORTANT:** For safety reasons the stall force setting will need to be adjusted for your particular application.
The Stall Force potentiometer on the control board operates like a volume control on a radio. Use a small flat blade screwdriver to adjust the potentiometer. Adjust the stall force from the MIN position until the gate operates smoothly without obstructing from its own weight or wind conditions.
**NOTE:** you may need to increase the stall force in cold temperatures due to increased resistance from gate hinges.
> Figure: Enlarged control-board illustration showing the STALL FORCE potentiometer. Circular detail is labeled “STALL FORCE,” “MIN,” and “MAX,” with curved arrows indicating adjustment direction. An arrow connects the enlarged detail to the potentiometer on the control board. Board labels include “AUTO CLOSE TIME,” “STALL FORCE,” “SOFT START OFF,” “WARNING — OFF,” “OPEN — PULL,” “2ND OPEN DLY.,” “MODE1 — OFF,” and “MODE2 — OFF.”
### Set Auto Close Time
The Auto-Close Time potentiometer controls the Auto-Close feature, and determines how long the gate will remain open (at the fully open position) before it begins to close. The settings for this feature are OFF, or from 3 to 120 seconds.
Adjust the Auto-Close potentiometer by using a small flat blade screwdriver.
> Figure: Control-board illustration with an enlarged potentiometer labeled “AUTO CLOSE TIME.” The dial is marked “OFF” and “120.” An arrow and label identify “Auto Close Time Potentiometer.” Nearby labels include “STALL FORCE,” “MIN,” “MAX,” “STATUS,” “LEARN RMT,” “LEARN MAST LIMIT,” and “LEARN 2ND LIMIT.”
LPA 3000XLS/3200XLS Instruction Manual 21
## Page 32
### Program Your Personal Transmitter Setting
All GTO transmitters are set to a standard code at the factory and are ready to operate your GTO gate operator. For your safety and security, we strongly recommend that you replace the factory setting with your own personal setting. Follow the directions below:
**NOTE:** If you have multiple transmitters, you should adjust all of them at this time. [RB741/RB742/RB743].
**Step 1**
Use a small phillips head screw driver to remove the transmitter cover.
**Step 2**
Set the transmitter DIP switches using a small screwdriver. There are nine (9) transmitter DIP switches (*RB741 only*); each can be placed in three different positions (+, 0, –). **DO NOT** set all the switches in the same position, such as all +, all 0, or all –. Once the DIP switches have been reset, replace and close the access cover.
**WARNING:** No other adjustments should be made inside the transmitter.
> Figure: Exploded illustration of a transmitter with cover removed. Interior labels include “LED” and battery marking “A23S 12V ALKALINE BATTERY.” Two screws are shown beside the open transmitter.
>
> Figure: Detail of nine transmitter DIP switches numbered 1 through 9. Position markings at left: “+,” “0,” and “–.” Label: “ECE.” A second perspective drawing shows the DIP-switch bank.
**Step 3**
Program the new setting into the control board:
A. Press and hold transmitter button.
B. Press and hold the LEARN RMT (Learn Remote) button on the control board until the alarm sounds.
C. Release transmitter button. The new code is stored in control board memory.
D. Release the LEARN RMT (Learn Remote) button.
**NOTE:** If you have purchased additional transmitters, program the settings for all at this time.
> Figure: Control-board illustration. An arrow points to the button labeled “LEARN RMT,” identified as “Learn Remote Button.” Other visible labels include “STATUS,” “LEARN MAST LIMIT,” “LEARN 2ND LIMIT,” “S3,” “S2,” and “S4.”
**Step 4**
**AT THIS POINT YOU SHOULD TEST RECEIVER RANGE BEFORE PERMANENTLY INSTALLING IT.**
> Figure: Troubleshooting Wizard mascot illustration beside text: “The Troubleshooting Wizard has detailed information this and other Installations.”
>
> Figure: Text: “24/7 Troubleshooting Wizard: http://support.gtoinc.com”
22 LPA 3000XLS/3200XLS Instruction Manual
## Page 33
# Dip Switch Settings
## DIP Switches
### DIP Switch Settings (MODES)
**DIP Switch #1: Soft Start/Stop**
ON– Soft start enabled (factory preset).
OFF– Soft start disabled.
The Soft Start/Stop feature slowly starts the gate as it begins to open and slows the gate as it comes to the closed position. This saves wear and tear on the gate and gate operator system.
**DIP Switch #2: Warning Buzzer**
ON– Buzzer warning enabled (factory preset).
OFF– Buzzer warning disabled.
The Warning Buzzer alerts you when the gate operator is beginning to either open or close the gate. It sounds for the first 2 seconds in each direction. It also sounds a warning when the gate obstructs two times in one cycle. Switching this to OFF only disables the open and close warning not the obstruction warning.
**DIP Switch #3: Push/Pull-to-Open**
ON– Push-to-open.
OFF– Pull-to-open (factory preset).
If your gate opens into the property the DIP Switch is set to the OFF position (factory setting). If your gate opens out from the property the DIP Switch must be set to the ON position. NOTE: if you have a Push-to-Open gate application you will need a Push-to-Open bracket (see Push-to-Open Instructions on page 26).
**DIP Switch #4: Dual Operation**
ON– Second opens simultaneously with master.
OFF– Second opens after master. (factory preset).
Note: Not applicable for single gate operator.
> Figure: Diagram of a four-position DIP switch and operator control board. Arrows identify switches 1–4. DIP switch orientation is labeled **ON**, **OFF**, and **DIP**. The board labels include **AUTO CLOSE TIME** with **OFF**, **120**, and **MIN**; **STALL FORCE** with **MIN** and **MAX**; **STATUS**; **LEARN RMT** (S3); **LEARN MAST LIMIT** (S2); and **LEARN 2ND LIMIT** (S4). Switch-setting legend reads: **SOFT START**—OFF/ON; **WARNING**—OFF/ON; **OPEN**—PULL/PUSH; **2ND OPEN**—DLY./SIMULT.; **MODE1**—OFF/ON; **MODE2**—OFF/ON.
## Page 34
# Connecting Accessories
## Input Connections
- All control inputs are dry-contact, normally open, inputs. DO NOT apply external voltage sources to these inputs.
- All inputs are connected with respect to COMMON terminal.
- The status LED will blink once when its corresponding input is activated.
**1 COM:** Circuit common (reference for all logic input)
- Two (2) terminals to provide extra common connection point.
**2 CYCLE/CLOSE:** (Typically for use with push button or hard-wired keypad)
- Each activation at this input will cycle the operation as follows:
OPEN–STOP–CLOSE–STOP–OPEN
**3 SAFETY:** (Typically for use with photo beam device, loop detector or other non-contact sensors)
- Activation of this input while the gate is closing will cause the gate to stop and return to the opened position.
- Activation of this input while the gate is opening has no effect (gate will continue to open).
- Activation of this input while gate is idle will prevent gate from closing.
**4 EXIT/OPEN:** (Typically for use with exit loop or wand)
- Activation of this input will open the gate if it’s not already at the open position.
- Activation of this input while at open limit will restart the auto close time (if enabled).
- Activation of this input while gate is idle will prevent gate from closing.
**5 SHADOW LOOP:** (Typically for use with loop detector)
- This input is only monitored when the gate is at the fully open position. At any other position, activation of this input has no effect on gate operation.
- Activation of this input while gate at the fully open position will prevent gate from closing.
**6 CLOSE EDGE:** (Typically for use with safety edge device)
- Activation of this input while the gate is closing will cause the gate to stop and reverse direction for approximately 2 seconds.
- Activation of this input while the gate is opening has no effect (gate will continue to open).
- Activation of this input while gate is idle will prevent gate from closing.
**7 OPEN EDGE:** (Typically for use with safety edge device)
- Activation of this input while the gate is opening will cause the gate to stop and reverse direction for approximately 2 seconds.
- Activation of this input while the gate is closing has no effect (gate will continue to close).
- Activation of this input while gate is idle will prevent gate from opening.
> Figure: Control-board terminal diagram with numbered arrows 1–7. Terminals, top to bottom, are labeled **COM**, **COM**, **CYCLE**, **SAFETY**, **EXIT**, **SHADOW**, **CLOSE EDGE**, and **OPEN EDGE**. A vertical label reads **CONTROL INPUTS**. Receiver terminals below are labeled **GTO RCVR.** with wire labels **GRN**, **BLK**, and **RED**; adjacent labels include **RECEIVER** and **ALM**.
## Page 35
# Wiring Accessories
> Figure: Wiring diagram for accessories connected to the operator control board. Board sections are labeled **POWER INPUT**, **CONTROL OUTPUTS**, **2ND OPERATOR**, **MASTER OPERATOR**, **CONTROL INPUTS**, **RECEIVER**, and **ALM**. Power input is labeled **GTO 18 VOLT TRANSF. OR SOLAR PANEL**. Control outputs include **LOCK PWR** and **AUX RLY**. Operator wire terminals are labeled **BLU**, **BRN**, **ORG**, **RED**, **BLK**, **GRN**, **WHT**, **BLU**, **BRN**, **ORG**, **RED**, and **BLK**. Control-input terminals are numbered 1–7 and labeled **COM**, **COM**, **CYCLE**, **SAFETY**, **EXIT**, **SHADOW**, **CLOSE EDGE**, and **OPEN EDGE**. Receiver wires are **GRN**, **BLK**, and **RED**.
>
> The diagram shows: **Automatic Gate Lock (FM144 & FM142)** wired to LOCK PWR; **Push Button Control (RB101)** wired to terminals 1 and 2; **Digital Keypad (F310)** wired to terminals 1 and 2; **Photo Beams (R4222)** wired to terminals 3 and 1; **Vehicle Sensor (FM139)** wired to terminals 4 and 1, with note “Refer to Vehicle Sensor manual for additional connections.” An **Edge Sensor** connects to terminal 1 and, according to application, terminal 6 or 7. Note: “There may be additional connection options for applications that are not illustrated here. Refer to accessory manuals for details.”
## Connecting Other Auxiliary Devices (Sirens, Lights, etc.)
- These 2 terminals are normally open “dry-contact” (no voltage) relay output.
- Relay is closed when gate is in motion; relay is open when gate is not moving.
- These 2 terminals maximum rating is 24Vdc, 1 Amp.
> Figure: Two-terminal relay output labeled **AUX RLY**.
## Page 36
# Push-To-Open Installation Information
**Swinging gates shall not open into public access areas!**
A “Push-to-Open” gate opens out from the property (operator arm extends to open the gate). A Push-To-Open installation requires the purchase of a Push-To-Open Bracket [R4388].
**In a Push-To-Open installation the operator is installed while the gate is in the CLOSED POSITION.**
## Install the Operator
Follow directions for installing the 3000XLS beginning on page 7. *The Push-To-Open installation differs from the Pull-To-Open installation in the following ways:*
1. In a Push-To-Open installation, the arm fully extends to open the gate, and it fully retracts to close the gate. (C)
2. You will install the operator while the gate is in the **CLOSED POSITION (arm fully retracted).** (A)
3. You must use the Push-to-Open Post Pivot Bracket [R4388] in the Post Bracket assembly. (B)
4. IMPORTANT: While determining the mounting point for the post pivot bracket assembly be sure that the position allows for 2” clearance between the gate and the operator in both the open and closed positions (see diagram below). This clearance will give the operator the most efficient leverage point for opening and closing the gate and more importantly provides the least possible pinch area. (C)
> Figure: Diagram A, labeled **Gate In Closed Position**. A gate operator is mounted between a fence post and a closed gate. Labels identify **Level Operator**, **Clevis Pin, Bushing, and Hairpin Clip**, and **Fence Post**.
> Figure: Diagram B, exploded mounting drawing of the Push-to-Open post pivot bracket assembly. Labels identify **3/8" x 3" Bolt**, **3/8" Washer** (two), **Post Bracket**, **3/8" Lock Washer**, **3/8" Nut**, and **Push-To-Open Post Pivot Bracket [R4388]**.
> Figure: Diagram C showing gate/operator positions and pinch clearances. The open-position view is labeled **Gate in the Open Position**, **Pinch Area**, **Clamp**, and **MAX 16"**. The closed-position view is labeled **Gate in the Closed Position**, **Pinch Area**, and **Clamp**. Both views specify **2" minimum** clearance between the gate and operator.
## Install the 3200XLS Operator
**Now install the SECOND gate operator on the SECOND gate in the same manner.**
> Figure: Wizard illustration beside troubleshooting information.
The Troubleshooting Wizard has detailed information on Push-To-Open Installations.
**24/7 Troubleshooting Wizard: http://support.gtoinc.com**
## Page 37
**Set Control Board for Push-To-Open**
Make sure the control box power switch is OFF. Use a small screwdriver to move the Number 3 DIP switch from the factory setting (OFF / Pull-To-Open) to ON for Push-To-Open. Turn power switch ON. The control board is now configured to push the gate open.
> Figure: Control-board diagram with enlarged DIP switch. Labels: “DIP#3”; “ON Push-to-open operation.”; “OFF Pull-to-open operation (factory setting).” Switch positions marked ON and OFF. Arrow identifies DIP switch 3 on the control board.
**Setting the Open Position Limit (Push-To-Open Installations)**
**Step 1**
Power switch is on, gates are in the **CLOSED** position, operator arms fully retracted.
> Figure: Photograph/drawing of control-box ON/OFF power switch.
>
> Figure: Double-gate diagram labeled “Gates in CLOSED Position,” with “Master Gate Operator,” “Second Gate Operator,” and “Control Box.” Both operator arms are retracted.
**Step 2**
Press the transmitter to activate operator arms. The gates will begin to open.
> Figure: Handheld transmitter drawing.
>
> Figure: Double-gate diagram labeled “Gates Opening,” with curved arrows showing both gates opening. Labels: “Master Gate Operator,” “Second Gate Operator,” and “Control Box.”
**Step 3**
When either gate reaches **OPEN** position, press transmitter to stop the gates.
**A.** If the master gate reaches open position first - press and hold LEARN MAST LIMIT for 5 seconds, or until buzzer beeps to set open position.
**B.** If the second gate reaches open position first - press and hold LEARN 2ND LIMIT for 5 seconds, or until buzzer beeps to set open position.
> Figure: Gate diagram labeled “Master Gate A in the Open Position,” with a left-pointing arrow. Text: “Follow B directions if second gate reaches open position first.”
>
> Figure: Transmitter drawing and two control-board button details. Detail A is labeled “LEARN MAST LIMIT,” “A.” and “Learn Master Limit Button,” with arrow to the button. Detail B is labeled “LEARN 2ND LIMIT,” “B.” and “Learn 2ND Limit Button,” with arrow to the button.
**Step 4**
Press the transmitter to **CLOSE** the gates. Gates will close fully. The gate in Step 3A or 3B is now programmed.
> Figure: Transmitter drawing.
>
> Figure: Double-gate diagram labeled “Gates in CLOSED Position,” with “Master Gate Operator,” “Second Gate Operator,” and “Control Box.” Both operator arms are retracted.
## Page 38
**Step 5**
Press the transmitter to activate operator arms. The gates will begin to **OPEN**.
> Figure: Transmitter drawing and double-gate diagram labeled “Gates Opening.” Curved arrows show both gates opening. Labels: “Master Gate Operator,” “Second Gate Operator,” and “Control Box.”
**Step 6**
The gate that was programmed in step 4 will stop on its own. Press the transmitter again to stop the other gate when it reaches the desired **OPEN** limit.
**A1.** Master gate reaches open postion - press and hold LEARN MAST LIMIT for 5 seconds, or until buzzer beeps to set open postion. (Master gate is now programmed)
**B1.** 2nd gate reaches open postion - press and hold LEARN 2ND LIMIT for 5 seconds, or until buzzer beeps to set open postion. (Second gate is now programmed)
> Figure: Gate diagram labeled “2nd Gate B1 Opening,” with a right-pointing arrow. Text: “Follow A1 directions to program master gate open position.”
>
> Figure: Transmitter drawing and control-board button details. Detail A: “LEARN MAST LIMIT,” “A.” and “Learn Master Limit Button.” Detail B: “LEARN 2ND LIMIT,” “B.” and “Learn 2ND Limit Button.” Arrows identify the respective buttons.
**Step 7**
Press the transmitter once again to close gates. Both gates open position are now programmed.
If you make a mistake and set the limit at the wrong position: press your transmitter to return the gates to the fully closed position, then press and hold the LEARN MAST LIMIT and/or the LEARN 2ND LIMIT button for 5 seconds. This will clear the memory for the open limit position. Repeat Steps 1-6
**Column Installation**
If this operator will be used with gates that are mounted on masonry, brick, or rock (etc.) columns, read the following carefully before proceeding
**A.** The simplest solution is to install the operator in a push-to-open configuration. The minimum clearance is easier to achieve and clearance is no longer a problem, since the operator will be pushing the gate away from the column instead of pulling it toward the column. It is recommended that you place a steel plate between the operator mounting brackets and masonry surface for additional strength.
**B.** If a push-to-open installation is impossible due to traffic hazards, terrain, etc., another option is to re-hang the gate. You may hang it on a post, either in the center of the column or at the back corner, or move the gate to the back corner of the columns.
**C.** The most difficult solution is to cut a notch in the column to accommodate the operator and power cable. This job is NOT for the inexperienced!*
> Figure: Column mount example diagram. Labels: “Column,” “Hinge,” “Gate,” and “Pivot Bracket.” Dimensions A and B are shown with dashed extension lines. Text: “Column Mount Example (A + B can not exceed 16 inches) Example: If A is 7" then B cannot exceed 9".”
> Figure: Small wizard illustration beside footnote.
*The Troubleshooting Wizard has detailed information on column mounting.
## Page 39
**Troubleshooting Guide**
If your gate operator does not function properly after it is installed, use this guide before calling the GTO Service Department.
**Generation 3 Audible Feedback**
| SYMPTOM | DIAGNOSIS | CHECK: |
|---|---|---|
| 1 short beep upon power up | Circuit Board Powered Up & Ready | • Normal Operation |
| 1 short beep upon activation | Blown Fuse<br><br>Low or Bad Battery<br><br>Loose Battery Connection | • Fuse<br>• Battery Under Load<br>• Battery Harness Connections |
| Continuous Uninterrupted Alarm | Circuit Board Senses an Obstruction | • Path of Gate<br>• Gate for Level and Plumb<br>• Stall Force Adjustment<br>• Disconnect Safety Devices<br>• Rev Counter |
| 1 beep with 10 seconds off | Low Battery Condition | • Fuses<br>• Battery Harness Connections<br>• Battery Under Load |
| 1 beep then 2 beeps | Master Motor Terminals Shorted | • Connections to Master Inputs<br>• Master Arm Power Cable<br>• Motor<br>• Circuit Board |
| 1 beep then 3 beeps | Second Motor Terminals Shorted | • Connections to Second Inputs<br>• Second Arm Power Cable<br>• Motor<br>• Circuit Board |
| 1 beep with 2 seconds off | Master Arm Limit Switch Error | • Connections to Master Inputs<br>• Master Arm Power Cable |
| 2 beeps with 2 seconds off | Second Arm Limit Switch Error | • Connections to Second Inputs<br>• Second Arm Power Cable |
| 3 beeps with 2 seconds off | Master Arm Rev Counter Error | • Connections to Master Inputs<br>• Master Arm Power Cable<br>• Rev Counter |
| 4 beeps with 2 seconds off | Second Arm Rev Counter Error | • Connections to Second Inputs<br>• Second Arm Power Cable<br>• Rev Counter |
## Page 40
**Generation 3 Visual Feedback**
| SYMPTOM | DIAGNOSIS | CHECK: |
|---|---|---|
| Status (clear) 1 blink | Cycle Terminal Shorted | • Disconnect the push button, keypad, intercom keypad, or any other accessory wired to this terminal.<br>• Try the remote. If the remote works, then the problem is the accessory. |
| Status (clear) 2 blinks | Safety Terminal Shorted | • Disconnect the loop detector, photo beam, or any other accessory wired to this terminal.<br>• Try the remote. If the remote works, the problem is the accessory. |
| Status (clear) 3 blinks | Exit Terminal Shorted | • Disconnect exit wand, loop detector, photo beam, or any other accessory wired to this terminal.<br>• Try remote. If the remote works, the problem is the accessory. |
| Status (clear) 4 blinks | Shadow Terminal Shorted | • Disconnect the loop detector, photo beam, or any other accessory wired to this terminal.<br>• Try remote. If the remote works, the problem is the accessory. |
| Status (clear) 5 blinks | Close Edge Terminal Shorted | • Disconnect the edge sensor, photo beam, or any other accessory wired to this terminal.<br>• Try the remote. If the remote works, the problem is the accessory. |
| Status (clear) 6 blinks | Open Edge Terminal Shorted | • Disconnect edge sensor, photo beam, or any other accessory wired to this terminal.<br>• Try the remote. If the remote works, the problem is the accessory. |
| RF (yellow) Flickers | Receiving 318 MHz RF | • Normal operation when remote or wireless keypad is used. |
| RF (yellow)OFF | No 318 MHz RF Received | • Battery in Remote<br>• Program Remote<br>• Antenna Receiver Connections<br>• Antenna Receiver |
| Power (green) ON | AC or Solar Power Present | • Normal Operation |
**VOLTAGE READINGS**
| | |
|---|---|
| 18 Vac Transformer | 18.0 to 22.0 Vac |
| 10 W Solar panel (single) | 18.0 to 22.0 Vdc |
| *In FULL SUN — measure voltage with the Solar Panel Disconnected.* | |
| 12 V, 7 amp hour Battery<br>or Two 12V, 7 amp hour Batteries if using solar power | 12.5 to 13.5 Vdc |
| *Measure voltage at battery terminals with battery disconnected* | |
| Charging circuit | 12.0 to 14.8 Vdc |
| *Measure voltage at battery terminals with battery connected* | |
## Page 41
> Figure: Black banner with white text: “Repair Service”.
If your LPA 3000XLS/3200XLS Gate Operators are not operating properly, please follow the steps below:
1. First use the procedures found in the Troubleshooting Guide (see page 29).
2. Use the 24/7 Troubleshooting Wizard at http://support.gtoinc.com.
3. If you are unable to solve the problem, call the LPA Service Department at (800) 543-1236. Refer to the serial number (located on the right side of the control box) and date of purchase when calling for assistance.
4. If repair or replacement of your gate operator is necessary, the Service Department will assign a Return Goods Authorization (RGA) number to you.
5. Once you have received your RGA# you are required to send in your original equipment for repair. Please refer to Manufactures’ Limited Warranty for complete details. Securely pack the component(s) authorized for return to the factory. Include a copy of your sales reciept for the purchase of the product(s). Write the RGA number issued to you on the outside of the package in LARGE BOLD PRINT.
Ship the package(s) freight prepaid to: GTO, 3121 Hartsfield Road, Tallahassee, Florida, USA 32303.
**NOTE: Products returned to GTO without a Return Goods Authorization (RGA) number in LARGE BOLD PRINT on the outside of the package WILL NOT be accepted. Also, items returned to GTO freight collect WILL NOT be accepted.**
### LPA Technical Service
**8:00am–7:00pm • Monday–Friday (EST)**
> Figure: GTO Access Systems, LLC logo. Text below: “3121 Hartsfield Road • Tallahassee, Florida, USA 32303”; “800-543-4283 • Fax (850) 575-8912”; “Web site www.linearproaccess.com”; “24/7 Troubleshooting Wizard: http://support.gtoinc.com”. Small wizard illustration at left of the final line.
LPA 3000XLS/3200XLS Instruction Manual 31
## Page 42
> Figure: Black banner with white text: “Accessories for 3000XLS/3200XLS”.
Please visit www.gtoaccess.com for photos and detailed descriptions of LPA Accessories. Or call 1-800-543-GATE (4283).
### POWERING ACCESSORIES
> Figure: Drawing of a coil of low-voltage wire.
**Low Voltage Wire** [RB509]
The 16 gauge, stranded, dual conductor low voltage Wire is for connecting the AC powered transformer, solar panel or wired accessories to the system’s control board. This specially designed wire is UV treated, PVC coated, and ready for direct burial.
> Figure: Drawing of a solar panel on a post.
**Solar Panel Kits** [FM122/FM123]
If your gate operator is more than 1000 ft. away from an AC power outlet, you can choose to maintain the battery charge with the GTO Solar Panel Kit.
- 10 Watt Solar Panel Charging Kit [FM123]
- 5 Watt Solar Panel Charging Kit [FM122]
> Figure: Drawing of a battery.
**Additional/Replacement Battery** [RB500]
For additional battery power or replacement.
### “FROM VEHICLE” ENTRY AND EXIT ACCESSORIES
> Figure: Drawings of a single-button transmitter and a dual-button transmitter on a key ring.
**Transmitters** [RB741/RB742/RB743]
Purchase an additional transmitter for each vehicle in your family. The Two-Button Transmitter can be programmed to operate both your gate operator and a garage door opener using the Universal Receiver. Or it can be programmed to open two gate operator systems.
- Single Button Transmitter [RB741]
- Dual Button Transmitter [RB742]
- Three Button Transmitter [RB743]
> Figure: Drawing of a Universal Antenna Receiver with a long vertical antenna.
**Universal Receiver** [RB709U-NB]
The Universal Antenna Receiver gives you the ability to use one remote to activate your gate operator and your garage door opener. Connects to any brand garage door opener. Up to 100 ft. range.
> Figure: Drawing of a Digital Keypad. Readable keypad labels: 1, 2 ABC, 3 DEF, 4 GHI, 5 JKL, 6 MNO, 7 PRS, 8 TUV, 9 WXY, 0.
**Digital Keypad** [F310]
Allow friends access to your property using an identification code that you provide. Program up to 25 entry codes for added security. Powered by three “AA” batteries (not included).
32 LPA 3000XLS/3200XLS Instruction Manual
## Page 43
> Figure: Drawing of a gooseneck pedestal, a residential wireless entry intercom unit, and its base station.
**Residential Wireless Entry Intercom** [F3100MBC]
Designed for added security to your automated gate with the ability to “speak to” and “screen” visitors safely from inside your home. Ideal for securing gate entrances while providing controlled access.
**Gooseneck Pedestal** [F100/F110]
Designed to mount digital keypads, wireless intercom systems, and other access control devices for your gate automation system.
### “HANDS FREE” ENTRY & EXIT ACCESSORIES
> Figure: Drawing of a driveway vehicle sensor: a long cylindrical sensor with coiled wire.
**Driveway Vehicle Sensor** [FM139]
Automatically activates gate operator “Hands-Free” when a vehicle exits the property. Electromagnetic sensor detects vehicles in motion.
- 50 ft. [FM139]
- 100 ft. [FM140]
- 150 ft. [FM141]
- 250 ft. [FM141-250]
> Figure: Drawing of a wireless vehicle sensor with upright antenna, cable, transmitter/receiver device, and horizontal sensor.
**Wireless Vehicle Sensor** [R4500]
Automatically activates gate operator “Hands-Free” when a vehicle exits the property. 100 ft. range between transmitter and receiver. Easy installation.
### LOCKING & SECURITY ACCESSORIES
> Figure: Drawings of an Automatic Gate Lock and its receiver bracket. Readable label on lock: “GTO AUTOMATIC GATE LOCK”.
**Automatic Gate Lock** [FM144/FM142]
The #1 Accessory For Swing Gate Operators! Designed for added security in conjunction with GTO Automatic Gate Operators. The gate lock unlocks and locks automatically when the gate opens and closes. The perfect solution for high wind conditions.
> Figure: Drawings of a Bulldog Pedestrian Gate Lock, keypad, and receiver bracket. Readable label on lock: “Bulldog”.
**Bulldog Pedestrian Gate Lock** [FM145]
Designed to mount on horizontal swing “walk through” wood, chain link, and metal pedestrian gates opening in or out. Ideal for securing pools, condominiums, schools and any pedestrian gate.
> Figure: Drawing of a wireless driveway alarm sensor with antenna and a base station.
**Wireless Driveway Alarm** [R4450].
This device alerts you of vehicles entering your driveway (with or without an automated gate). The indoor base station signals you with a door chime when a vehicle passes the driveway sensor.
LPA 3000XLS/3200XLS Instruction Manual 33
## Page 44
### ADDITIONAL ACCESSORIES
> Figure: Drawing of two Photo Beam units.
**Photo Beams** [R4222]
Primary “through beam” photo beam device. Provides “non-contact” entrapment protection.
> Figure: Drawing of a Pin Lock.
**Pin Lock** [FM345]
Use as a substitute for the clevis pin at the front mount of the PRO-SW3000XLS to prevent theft of the operator.
- Pin Lock 10-pack: ten Pin Locks keyed alike [FM345KA].
> Figure: Drawing of an unlit Push Button Control.
**Push Button Control** [RB101]
Wire this unlit push button directly to your gate operator for simple open/close/stop operation from up to 1000 ft. away. Use 16 gauge low-voltage wire.
> Figure: Drawing of a Replacement Transformer.
**Replacement Transformer** [RB570]
Standard 18 volt, 2200 mA AC transformer included with the 3000XLS to maintain battery charge.
> Figure: Drawing of a Gate Grounding Kit with coiled cable and connectors.
**Gate Grounding Kit** [R4196]
The purpose of the grounding kit is to REDUCE THE RISK of damage to electronic equipment from lightning strikes. There is no protection or grounding system that can completely eliminate this risk.
### HARDWARE ACCESSORIES
> Figure: Drawing of a Push To Open Bracket.
**Push To Open Bracket** [R4388]
Required when the 3000XLS must push a gate open (arm extends to open), such as away from a sloping driveway or where space prevents gate from opening into the property (pull to open). Order two brackets for a dual swing gate installation.
> Figure: Drawing of a Column Mount Lock Receiver.
**Column Mount Lock Receiver** [433IH]
For use with the Automatic Gate Lock or Bulldog Pedestrian Gate Lock when mounting on brick columns or applications with limited space.
> Figure: GTO Access Systems, LLC logo. Text below: “3121 Hartsfield Road • Tallahassee, Florida, USA 32303”; “800-543-4283 • Fax (850) 575-8912”; “Web site www.linearproaccess.com”; “24/7 Troubleshooting Wizard: http://support.gtoinc.com”. Small wizard illustration at left of the final line.